ASHRAE 62.1 - Indoor Air Quality Procedure (IAQP) 2025
- David Mallinson

- Nov 9, 2025
- 2 min read
A Technical Explainer for Architects & Consulting Engineers
The purpose of IAQP
ASHRAE Standard 62.1 provides two compliant ventilation pathways:
Ventilation Rate Procedure (VRP) – prescriptive outside air volumes
Indoor Air Quality Procedure (IAQP) – performance-based contaminant control
The IAQP allows engineers to meet indoor air quality requirements by limiting contaminant concentrations, rather than by supplying fixed quantities of outdoor air.
This enables safe reduction of outdoor air, provided that:
Contaminants of concern are identified
Acceptable concentration limits are defined
Control strategies are documented and verifiable.
Why ASHRAE 62.1 - Indoor Air Quality Procedure Matters in HVAC Design
In hot-climate regions, outdoor air dominates:
Cooling load
HVAC system sizing
Energy consumption
IAQP enables engineers to decouple IAQ performance from outside air volume, unlocking opportunities to:
Reduce ventilation rates
Downsize HVAC equipment
Lower peak and annual energy demand
IAQP Compliance Framework (An Engineer's Viewpoint)
Under ASHRAE 62.1 - Indoor Air Quality Procedure, the design team must demonstrate that:
Contaminants of Concern are identifiedTypical examples:
Particulates (PM2.5, PM10)
VOCs
Microbial contaminants (bacteria, viruses, mould)
Odours
Acceptable Concentration Limits are defined using:
ASHRAE guidance
WHO / EPA references
Owner Project Requirements (OPR)
Control Measures are implemented including:
Filtration
Air cleaning / purification
Source control
Ventilation (reduced but sufficient)
Performance is Achieved and Maintained through:
Independently tested technologies
Monitoring (optional but recommended)
Documented design intent
The Role of Bipolar Ionization in IAQP
When Direct Barrier Discharge (DBD) Bipolar Ionization is integrated into the HVAC system:
Pathogens, VOCs, and fine particulates are neutralized in the air and on surfaces
Contaminant concentrations are actively reduced, not just diluted
IAQ targets can be met with significantly less outside air
This allows engineers to justify ventilation reductions often in the order of ~40–50%, subject to project-specific modelling and approval.
HVAC Downsizing Opportunities Enabled by IAQP
Reducing outside air directly impacts system sizing:
System Element | Impact |
FAHUs | Lower airflow rates |
Cooling coils | Reduced sensible & latent loads |
Chillers | Smaller capacity |
Ductwork | Reduced cross-sectional area |
Plant rooms | Smaller footprint |
Electrical | Reduced fan & chiller power |
The result is lower HVAC CapEx and lower OpEx, while remaining compliant with ASHRAE 62.1.
Energy & Sustainability Implications
Typical outcomes in IAQP + air purification designs:
~10–15% reduction in total building energy
Reduced peak cooling demand
Lower carbon emissions
Improved LEED, WELL, and Fitwel alignment
Importantly, IAQP is explicitly recognised within these certification frameworks as a valid compliance pathway.
Key Engineering Considerations
IAQP must be documented clearly in Basis of Design (BoD)
Air cleaning technology must be independently tested and ozone-free
Coordination with sustainability consultants is recommended
Early-stage integration (concept / schematic) maximises savings
Summary for Engineers
IAQP is not a workaround.It is a standards-compliant, performance-based design method that:
Improves IAQ
Reduces HVAC size
Cuts energy use
Strengthens the business case for healthy buildings
When paired with proven air purification, IAQP becomes a powerful engineering optimisation tool.




Comments